Taylor K-1645-2
Boiler/Cooling Systems, Alkalinity/Chloride/Hardness
ChemWorld is a distributor of Taylor Technologies Test Kits and Reagents. Order directly online and save today.
DROP TEST HARDNESS - TOTAL
COMPONENTS:
1 x 5067B Instruction
1 x 9198B Sample Tube, Graduated, 25 mL, plastic w/cap
and blue dot
1 x R-0619B-C Hardness Buffer (blue cap), 2 oz, DB
1 x R-0620B-I Hardness Indicator Powder (blue cap), 10 g
1 x R-0683-C Hardness Reagent, 2 oz, DB.
Hardness-total (Drop Test)
1. Rinse and fill 25 mL sample tube (#9198B) to 25 mL mark
with water to be tested.
2. Add 5 drops R-0619B Hardness Buffer. Swirl to mix.
3. Add 1 dipper R-0620B Hardness Indicator Powder. Swirl until
dissolved. If hardness is present, sample will turn red.
4. Add R-0683 Hardness Reagent dropwise, swirling and counting
after each drop, until color changes from red to blue.
Always hold bottle in vertical position.
5. Multiply drops of R-0683 Hardness Reagent by 10. Record as
parts per million (ppm) total hardness as calcium carbonate.
DROP TEST ALKALINITY - PM/PT
COMPONENTS:
1 x 5067G Instruction
1 x 9198G Sample Tube, Graduated, 25 mL, plastic w/cap
and green dot
1 x R-0637-C Methyl Orange Indicator, 2 oz, DB
1 x R-0638G-A Phenolphthalein Indicator (green cap), .75 oz, DB
1 x R-0645-C Total Alkalinity Indicator, 2 oz, DB
1 x R-0687G-C Sulfuric Acid .12N (green cap), 2 oz, DB.
Alkalinity-P/M (Drop Test)
1. Rinse and fill 25 mL sample tube (#9198G) to 25 mL mark with
water to be tested.
2. Add 3 drops R-0638G Phenolphthalein Indicator. Swirl to mix.
Sample will turn pink if P alkalinity is present--proceed to
Step 3. If no pink color, go to Step 4.
3. If pink, add R-0687G Sulfuric Acid .12N dropwise, swirling
and counting after each drop, until color changes from
pink to colorless. Record drops as P reading. Always hold
bottle in vertical position.
4. Add 5 drops R-0637 Methyl Orange Indicator. Swirl to mix.
Sample should turn yellow.
5. Continue adding R-0687G Sulfuric Acid .12N dropwise, swirling
and counting after each drop, until color just changes from
yellow to orange (salmon pink). Record total drops (Steps
3 and 5) as M reading. Always hold bottle in vertical
position.
6. Multiply P reading by 10. Record as parts per million (ppm)
P alkalinity as calcium carbonate. Multiply M reading by 10.
Record as ppm M alkalinity as calcium carbonate.
Alkalinity-P/T (Drop Test)
1. Rinse and fill 25 mL sample tube (#9198G) to 25 mL mark with
water to be tested.
2. Add 3 drops R-0638G Phenolphthalein Indicator. Swirl to mix.
Sample will turn pink if P alkalinity is present--proceed
to Step 3. If no pink color, go to Step 4.
3. If pink, add R-0687G Sulfuric Acid .12N dropwise, swirling and
counting after each drop, until color just changes from pink
to colorless. Record drops as P reading. Always hold bottle in
vertical position.
4. Add 5 drops R-0645 Total Alkalinity Indicator. Swirl to
mix. Sample should turn green.
5. Continue adding R-0687G Sulfuric Acid .12N dropwise, swirling
and counting after each drop, until color changes from green
to red. Record total drops (Steps 3 and 5) as T reading.
Always hold bottle in vertical position.
6. Multiply P reading by 10. Record as parts per million (ppm)
P alkalinity as calcium carbonate. Multiply T reading
by 10. Record as ppm T alkalinity as calcium carbonate.
DROP TEST CHLORIDE
COMPONENTS:
1 x 5067O Instruction
1 x 9198O Sample Tube, Graduated, 25 mL, plastic w/cap
and orange dot
1 x R-0630-C Chromate Indicator, 2 oz, DB
1 x R-0638O-A Phenolphthalein Indicator (orange cap),
.75 oz, DB
1 x R-0687O-C Sulfuric Acid .12N, (orange cap), 2 oz, DB
1 x R-0706-C Silver Nitrate Reagent, 2 oz, DB.
Chloride (Drop Test)
NOTE: When sulfite content of sample water to be tested
exceeds 10 ppm, the sulfite should be oxidized to
prevent interference in test. A 25 mL water sample
is first adjusted to the appropriate pH, then 1 mL
(or 24 drops) of R-0649 3% Hydrogen Peroxide Solution
(sold separately) is added and thoroughly mixed.
Continue with the rest of the procedure.
1. Rinse and fill 25 mL sample tube (#9198O) to 25 mL mark
with water to be tested.
2. Add 2 drops R-0638O Phenolphthalein Indicator. Swirl to
mix. If sample turns red, add R-0687O Sulfuric Acid .12N
dropwise, swirling after each drop, until color changes
from red to colorless.
3. Add 5 drops R-0630 Chromate Indicator. Swirl to mix.
Sample should turn yellow.
4. Add R-0706 Silver Nitrate Reagent dropwise, swirling and
counting after each drop, until color changes from yellow to
milky salmon (brick) red. Always hold bottle in vertical
position.
NOTE: Do not add enough R-0706 Silver Nitrate Reagent to give a
brown color. First change from yellow to a milky salmon
(brick) red is the endpoint.
5. Multiply drops of R-0706 Silver Nitrate Reagent by 10.
Record as parts per million (ppm) chloride.
This product ships within approx. 5 to 7 business days from the state of Maryland. Listed below is the shipping transit time for 2024. UPS transit map - This product only ships UPS. We can not ship this product via Fedex or USPS.
- We can ship internationally.
- We can not ship this product to a PO box.
- If the product is Haz mat. It can not can not ship this via Air.
You will receive the tracking info after the order ships within 48 to 72 hours. We do not offer expedited shipping for this product.
If you can not order online, call in your order at 800-658-7716.
|
|
|
|
|
|
|