DROP TEST PERACETIC ACID (0-1000 ppm)
COMPONENTS:
2 x 4030 Pipet, Calibrated 0.5 & 1.0 mL, plastic w/cap
1 x 4078 Pipet, Graduated, 3 mL (0.5 mL div.), plastic
1 x 5015 Instruction
1 x 9198 Sample Tube, Graduated, 25 mL, plastic w/cap
1 x R-0925 PAA Reagent #1
1 x R-0926 PAA Reagent #2, DB
1 x R-0927 PAA Reagent #3
1 x R-0928 PAA Reagent #4, DB
1 x R-0929 PAA Titrating Solution, DB.
NOTE: This test determines peracetic acid concentrations in systems
treated with products that contain only peracetic acid (up to
20%) and hydrogen peroxide (up to 30%) as the active ingredients.
The Product Factor (PF), calculated below, represents the
peracetic acid in the treatment product and is used to determine
the appropriate sample size for the test and to calculate the
peracetic acid concentration in the system. The percentages of
peracetic acid and hydrogen peroxide needed to calculate the PF
may be found on the treatment product label, MSDS, or Certificate
of Analysis.
Treatment Product Used ____________ Percent Peracetic Acid = __________
Percent Hydrogen Peroxide = _________
Calculate A:
A = Percent Peracetic Acid
_______________________ = ___________ = ______________ 38 38
Calculate B:
B = Percent Hydrogen Peroxide
____________________ = ___________ = ____________
17 17
Calculate PF:
PF = A -------------------
_____ = + = _________________
A+B
1. Select sample size from the chart below that corresponds to the
peracetic acid treatment range and calculated Product Factor (PF):
Treatment Range
Product Factor 0-10 10-100 100-300 300-1000
ppm ppm ppm ppm up to 0.15 25 mL 2.5 mL 1.0 mL ---
0.15 - 0.3 25 mL 5.0 mL 2.5 mL 1.0 mL
0.3 - 0.5 --- 10 mL 2.5 mL 1.0 mL
2. Rinse and fill 25 mL sample tube (#9198) to selected sample size
with water to be tested.
NOTE: For 1 mL and 2.5 mL samples, use a 3.0 mL pipet (#4078) to
collect and add desired sample to a clean, dry 25 mL sample tube.
3. Using a 1.0 mL pipet (#4030), add 0.5 mL R-0925 PAA Reagent #1.
Swirl to mix.
4. Add 5 drops R-0926 PAA Reagent #2. Swirl to mix. Sample will turn
a straw to yellow color if product is present.
5. Using another 1.0 mL pipet, add 0.5 mL R-0927 PAA Reagent #3.
Swirl to mix. Wait 15 seconds.
6. Add 5 drops R-0928 PAA Reagent #4. Swirl to mix. Sample will
turn deep blue.
7. Add R-0929 PAA Titrating Solution dropwise, swirling to mix
thoroughly and counting after each drop, until color just changes
from blue to colorless. Always hold bottle in vertical position.
8. Using the equation below, calculate peracetic acid concentration:
PAA = Drops R-0929 x 100
(_____________ x PF)
Sample size
Record as parts per million (ppm) Peracetic Acid (w/v)
NOTE: To convert peracetic acid (w/v) to (w/w), multiply ppm
peracetic acid (w/v) by the specific gravity of the
treatment product found on the product's label, MSDS, or
Certificate of Analysis.
This product ships within approx. 5 to 7 business days from the state of Maryland.
Listed below is the shipping transit time for 2024. UPS transit map - This product only ships UPS. We can not ship this product via Fedex or USPS.
- We can ship internationally.
- We can not ship this product to a PO box.
- If the product is Haz mat. It can not can not ship this via Air.
You will receive the tracking info after the order ships within 48 to 72 hours. We do not offer expedited shipping for this product.
If you can not order online, call in your order at 800-658-7716.
|
|
|
|
|
|
|