#1 in Distributing Specialty
Chemicals & Equipment

Email Us Today Free shipping on
all chemicals (48 states)

  Home > Boiler Chemicals >

Amine Steam Treatment Chemical - 5 to 55 Gallons
Steam Treatment Chemical
ChemWorld 1888 - Steam Treatment Chemicals
 
Alternative Views:


ChemWorld 1888 - Steam Treatment Chemicals
Our Price: $399.99
Sale Price: $299.99
Savings: $100.00


Quantity in Stock:29

Free Shipping
Availability: Usually Ships in 3 to 5 Business Days
Product Code: CHEMWORLD-1888


Steam Treatment*:


Drum Delivery Option*:


Qty:
Description Shipping & Transit Times
 

Steam Treatment Chemicals

What is ChemWorld 1888?
ChemWorld 1888 is a steam treatment chemical commonly referred to as amines. The three types of amines are cyclohexylamine, morpholine, and diethylaminoethanol (DEAE). Blends of the chemicals are commonly used. ChemWorld 1888 is a tri-blend amine and ideal for use in most steam boiler systems.

Why are Steam Treatment Chemicals used?
They are primarily used to increase the condensate pH. Low pH in condensate systems will lead to excessive corrosion and result in steam leaks and condensate leaks.

What chemical is recommended for the Treatment of Steam?
ChemWorld 1888 is a blend of cyclohexylamine, morpholine, and diethylaminoethanol (DEAE) neutralizing amines for use in a wide range of boiler condensate systems. ChemWorld 1888 is designed for extensive condensate systems having short and long steam distribution lines. The amine distribution ratios cover a wide range to provide good protection for all parts of these systems. ChemWorld 1888 is normally used in combination with other treatment chemicals to provide a complete program.

What are the benefits of ChemWorld 1888?
This product will improve boiler reliability and cleanliness while protecting the condensate piping from corrosion. It is also designed to protect all areas of extensive condensate systems.

How do you feed amines?
ChemWorld 1888 is normally fed continuously to the system being treated. However, shot feeding may be satisfactory in some circumstances. The product may be fed neat but is most often mixed in a chemical feed tank with the other materials required to complete the program. Good quality condensate, softened water, or feedwater should be used. This product should be injected near the center of the steam header with an retractable chemical injection quill. We always recommend automation by using a boiler conductivity controller.

What material of construction should be used when feeding this chemical?
All materials of construction making contact with the concentrated form of this chemical such as tanks, pumps, piping, and valves should be made of stainless steel or polyethylene.

What test should be performed to monitor the chemical performance?
ChemWorld 1888 is normally controlled by a pH test on the return condensate. For extensive distribution systems, samples should be taken from various points in the system at least until it can be assured the desired distribution of the amine is being achieved.

How should this product be handled?
Keep in a tightly closed container. Store indoors. Recommended storage temperature is 50 F - 105 F. Do not reuse container. Dispose of empty containers in compliance with federal, state/provincial and local laws and regulations.

What environmental, health, and safety?
For detailed information, consult the Safety Data Sheet (SDS).

What boiler test should I use on this chemical?
Monitor the condensate pH with pH test strips

For new steam boiler startups, consider purchasing our Steam Boiler Startup Kit.

Average Rating: Average Rating: 4 of 5 4 of 5 Total Reviews: 1 Write a review »

  0 of 0 people found the following review helpful:
 
4 of 5 It works! February 15, 2024
Reviewer: Anonymous Person from Havre, MT United States  
For years I have tolerated acidic condensate return.  Adding this to my condensate return/boiler feed tank raised the pH of my returning condensate to neutral or above.

Was this review helpful to you?